Featuring true on-line operation with pure sine wave output, zero transfer time to battery and complete UPS replacement capability with no downtime, the SU6000RT4UHV provides the highest level of protection available for mission-critical equipment from power outages, voltage fluctuations and transient surges. It converts incoming AC power to DC, and re-converts it back to filtered AC output with a pure sine wave, isolating connected components from all power problems in high-voltage environments. The SU6000RT4UHV has a 6kVA/5400W capacity and 4 AC outlets (2 L6-20R; 2 L6-30R).With its detachable PDU, the SU6000RT4UHV is easily hot-swappable by a user of any skill set—no need for lengthy and expensive service calls, and no downtime if a repair or battery replacement is needed. In bypass mode, the PDU passes power to equipment without the use of the power and battery modules, allowing them to be removed while keeping your application in operation. UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The SU6000RT4UHV‘s runtime can be expanded with optional external battery packs.The SU6000RT4UHV features a highly efficient (96%) economy mode setting that can significantly reduce a facility's energy costs by minimizing heat output, reducing cooling requirements and consuming less electricity.An LCD display with LED indicators enables IT personnel to monitor operating modes and conditions. The LCD/LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various conditions.The SU6000RT4UHV features a USB port and a DB9 port that, when used with Tripp Lite's included PowerAlert software, provide comprehensive network power monitoring and control. An optional SNMPWEBCARD accessory can enable the UPS to operate as an IP managed device.The unit requires only 4U of rack space in a standard rack enclosure and can be installed in a 2-post rack using the 2POSTRMKITHD accessory, or in a tower configuration with the 2-9USTAND accessory.The SU6000RT4UHV comes with $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only) for connected equipment and a 2-year warranty. - Tripp Lite SU6000RT4UHV 6000VA / 6kVA / 5400 watt online, double-conversion UPS system in a single 4U rack/tower compatible housing (at 208V nominal, output is limited to 4992 watts) - Full-time active power conditioning maintains clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise - Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions - Detachable back panel PDU contains input line cord connection and output receptacles, plus manual bypass switch to support hot-swappable whole UPS replacement with no interruption to connected equipment - L6-30P input plug; two L6-30R and two L6-20R outlets - Included rail kit supports 4U 19 inch rackmount installation in 4 post racks - Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (1 required for SU6000RT4UHV) - Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UHV) - Maximum installed rack depth of only 20.7 in. / 52.6cm
Specification:
Power |
---|
Output power | 5400 W |
Input operation voltage (min) | 200 V |
Input operation voltage (max) | 240 V |
Output operation voltage (min) | 208 V |
Output operation voltage (max) | 240 V |
Maximum current | 40 A |
Efficiency | 96% |
Emergency Power Off (EPO) | Yes |
Power factor | 0.9 |
Crest factor | 3:1 |
Output power capacity | 6 kVA |
Input frequency | 50/60 Hz |
Ports & interfaces |
---|
Cable length | 118.1" (3 m) |
AC outlets quantity | 4 AC outlet(s) |
AC outlet types | C19 coupler |
USB 2.0 ports quantity | 1 |
Serial ports quantity | 1 |
RS-232 ports | 1 |
Performance |
---|
Number of phases | 1 |
LED indicators | Yes |
EMI/RFI noise filtering | Yes |
Noise level | 60 dB |
Audible alarm(s) | Yes |
Features |
---|
Country of origin | China |
Output power | 5400 W |
Input operation voltage (min) | 200 V |
Input operation voltage (max) | 240 V |
Output operation voltage (min) | 208 V |
Output operation voltage (max) | 240 V |
Maximum current | 40 A |
Efficiency | 96% |
EMI/RFI noise filtering | Yes |
Emergency Power Off (EPO) | Yes |
Power factor | 0.9 |
Noise level | 60 dB |
Crest factor | 3:1 |
Audible alarm(s) | Yes |
Output power capacity | 6 kVA |
Input frequency | 50/60 Hz |
Number of phases | 1 |
Battery |
---|
Battery recharge time | 6 h |
Typical backup time at half load | 8.5 min |
Typical backup time at full load | 2 min |
Hot-swap battery | Yes |
Design |
---|
Country of origin | China |
Rack capacity | 4U |
Form factor | Rackmount |
LED indicators | Yes |
Product colour | Black |
Certification | UL1778 CSA FCC Part 15 Category A IEC 61000-4-5 1995 B |
Cable length | 118.1" (3 m) |
Display type | LED |
Operational conditions |
---|
Operating temperature (T-T) | 0 - 40 °C |
Storage temperature (T-T) | -15 - 50 °C |
Operating altitude | 0 - 118110.2" (0 - 3000 m) |
Technical details |
---|
Sustainability certificates | RoHS |
Weight & dimensions |
---|
Package width | 34" (863.6 mm) |
Package depth | 24" (609.6 mm) |
Package height | 30" (762 mm) |
Weight | 108 lbs (49 kg) |
Width | 17.5" (445 mm) |
Package weight | 190 lbs (86.2 kg) |
Height | 6.85" (174 mm) |
Depth | 20.7" (526 mm) |
Packaging data |
---|
Package width | 34" (863.6 mm) |
Package depth | 24" (609.6 mm) |
Package height | 30" (762 mm) |
Package weight | 190 lbs (86.2 kg) |
Logistics data |
---|
Products per master (outer) case | 1 pc(s) |
Master (outer) case width | 34" (863.6 mm) |
Master (outer) case length | 24" (609.6 mm) |
Master (outer) case height | 30" (762 mm) |
Master (outer) case gross weight | 190 lbs (86.2 kg) |
Certificates |
---|
Certification | UL1778 CSA FCC Part 15 Category A IEC 61000-4-5 1995 B |
Other features |
---|
Number of phases | 1 |
Input connection type | L6-30P |
Relative humidity | 0 - 95% |
Management platform | SNMP |