Remote Management Capabilities Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements. Local Current Monitoring Display The aggregate current draw per power distribution unit is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. Alarm Thresholds Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities. Please see SKU specifications for availability) Load indicator LED Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits. Integrates with InfraStruXure Central An IT-ready, scalable monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network Flash Upgradeable Quickly and easily upgrade firmware via network download for future product enhancements. Eliminates the need to replace products already installed in the field when new features are released. (Note: Networked units only)
Specification:
Design |
---|
PDU types | Metered |
Mounting | Horizontal/Vertical |
Product colour | Black |
Certification | cUL Listed, FCC Part 15 Class A, ICES-003, UL 60950-1, UL Listed |
Ports & interfaces |
---|
AC outlets quantity | 36 AC outlet(s) |
AC outlet types | NEMA 5–20R |
Power plug | NEMA L21-20P |
Features |
---|
Cable length | 72" (1.83 m) |
LED indicators | Yes |
Certification | cUL Listed, FCC Part 15 Class A, ICES-003, UL 60950-1, UL Listed |
Ergonomics |
---|
Cable length | 72" (1.83 m) |
LED indicators | Yes |
Power |
---|
Nominal input voltage | 208 V |
Nominal output voltage | 120 V |
Maximum total current draw per phase | 16 A |
Maximum input current per phase | 20 A |
Load capacity | 5760 VA |
AC input frequency | 50 - 60 Hz |
Weight & dimensions |
---|
Dimensions (WxDxH) | 2.17 x 1.73 x 70.5" (55 x 44 x 1791 mm) |
Weight | 13.3 lbs (6.04 kg) |
Package weight | 17.9 lbs (8.12 kg) |
Package dimensions (WxDxH) | 6.3 x 4.25 x 79" (160 x 108 x 2006 mm) |
Packaging data |
---|
Package weight | 17.9 lbs (8.12 kg) |
Package dimensions (WxDxH) | 6.3 x 4.25 x 79" (160 x 108 x 2006 mm) |
Operational conditions |
---|
Operating temperature (T-T) | -5 - 45 °C |
Storage temperature (T-T) | -25 - 65 °C |
Storage relative humidity (H-H) | 5 - 95% |
Operating relative humidity (H-H) | 5 - 95% |
Operating temperature (T-T) | 23 - 113 °F |
Operating altitude | 0 - 118110.2" (0 - 3000 m) |
Non-operating altitude | 0 - 590551.2" (0 - 15000 m) |
Technical details |
---|
Sustainability certificates | RoHS |